E6581381

H-6

8

(Continued)

Error code

Failure

code

Description

QER

0026

Overcurrent flowing in element during deceleration

QER

0027

Overcurrent flowing in element during constant-speed operation

GVP

0054

Auto-tuning error

GV[R

0029

Inverter type error

QJ

002E

External thermal input

G

0032

VIA cable break

G

0033

Communication error between CPUs

G

0034

V/F control error

G

0035

CPU fault 2

UQWV

002F

Step-out (for PM motors only)

Note: Past trip records (trip records retained or trips that occurred in the past) can be called up.

⇒ See section 8.1 "Status monitor mode" for the call-up procedure.
(*) Strictly speaking, this code is not an error code; this code is displayed to show the absence of error

when the past trip monitor mode is selected.

8.2.2 Display of trip information at the occurrence of a trip

At the occurrence of a trip, the same information as that displayed in the mode described in 8.1.1, "Status monitor
under normal conditions," can be displayed, as shown in the table below, if the inverter is not turned off or reset.
To display trip information after turning off or resetting the inverter, follow the steps described in 8.1.2, "Display of
detailed information on a past trip."

Example of call-up of trip information

Item displayed

Key

operated

LED

display

Communic
ation No.

Description

Cause of trip

QR

Status monitor mode (The code blinks if a trip
occurs.)
The motor coasts and comes to a stop (coast stop).

Parameter setting
mode

CWH

The first basic parameter “CWH” (Wizard function)
is displayed.

Direction of
rotation

HTH

FE01

The direction of rotation at the occurence of a trip
is displayed. (HTH: forward run, HTT:
reverser run).

Operation
frequency
command

H

FE02

The operation frequency command value (Hz/free
unit) at the occurrence of a trip is displayed.

Load current

E

FE03

The output power of the inverter at the occurrence
of a trip (%/A) is displayed.

Input voltage

[

FE04

The inverter input (DC) voltage (%/V) at the
occurrence of a trip is displayed.

Output voltage

R

FE05

The output voltage of the inverter at the
occurrence of a trip (%/V) is displayed.

(Continued overleaf)

Note 3

Note 2

Note 1

MODE

MODE