E6581381

F-47

6

[Selection 2: Setting vector control and manual tuning independently]

If an "GVP" tuning error is displayed during auto-tuning or when vector control characteristics are to be
improved, independent motor constants can be set.

Title

Function

Adjustment range

Default setting

H

Slip frequency gain

0-150 (%)

50

H

Automatic torque boost value

0.0-30.0 (%)

H

Motor rated current

0.1-200.0 (A)

H

Motor no-load current

10-100 (%)

H

Motor rated rotational speed

100-15000 (min

-1

)

Depends on the

capacity

(

⇒ See page K-14)

H

Speed control response
coefficient

1-150

40

H

Speed control stability
coefficient

1-100

20

Setting procedure Adjust the following parameters:

H

: Set the compensation gain for the slipping of the motor. A higher slip frequency reduces motor

slipping correspondingly. After setting H, set H to adjust in detail.

H

: Adjust the primary resistive component of the motor. Use the auto-tuning value.

H

: Set the rated current of the motor. For the rated current, see the motor's nameplate or test report.

H

: Set the ratio of the no-load current of the motor to the rated current. Enter the value in % that is

obtained by dividing the no-load current specified in the motor's test report by the rated current.

H

: Set the rated rotational speed of the motor. For the rated current, see the motor's nameplate or test

report.