MG 1000B platform hardware installation
5
Place the MG 1000B Core on the guide brackets. Carefully slide the
MG 1000B Core into the rack until the ear brackets come to rest
against the rack support.
6
Use the four remaining #12-24 self-tapping screws to fasten the MG
1000B Core to the rack supports (two screws on each side).
7
Make sure that the back of the MG 1000B Core is on the guide
brackets. See
Figure 71 "MG 1000B Core and MG 1000B Expander
installed in a rack" (page 226)
Figure 71
MG 1000B Core and MG 1000B Expander installed in a rack
8
Install the equipment ground wires for the MG 1000B Core, MG
1000B Expander, and Signaling Server. See Communication Server
1000E: Installation and Configuration (NN43041-310).
9
Install a UPS (if required) according to the manufacturer’s
instructions.
10
Open the MG 1000B Core and install the Software Daughterboard,
Security Device, and ground clip as described in Communication
Server 1000E: Installation and Configuration (NN43041-310).
11
Install circuit cards in the MG 1000B Core and the MG 1000B
Expander. See Communication Server 1000E: Installation and
Configuration (NN43041-310).
12
Make the Ethernet connections. Configure the Ethernet port to
enable TM 3.01 and Element Manager connectivity as required.
a. See
Procedure 22 "Connecting the Ethernet ports" (page 247)
.