Configuring the T1 Network
5-28
Access Manager 2000 User Manual
The
Use
field is used to assign a relative priority to an alarm path. To
view the available options, go to the
Use
field and press
. A pop up
menu will appear with these options:
SEND
The alarm will be reported to this alarm path.
BACKUP
The alarm will be sent to this path if the SEND path is
unable to deliver the alarm.
NONE
Alarms are not to be sent to this path.
The acceptable combinations of options for this field are listed below:
Based on the relative priorities you want to assign, enter your choices in
the
Primary
and
Secondary
columns.
Setting up alarm destination access
To set up alternate alarm paths, you’ll be using either a modem, a stat
mux, or an X.25 PAD to communicate with Access Manager.
You need to specify the:
■
type of device connected to the node controller
■
speed at which the device operates
■
address of the alarm destination
You must use the same com port access device and baud rate for both
alarm paths.
Primary
Secondary
Description
SEND
SEND
Send to both addresses specified
SEND
BACKUP
Send to Secondary address only if Primary address is unavailable
BACKUP
SEND
Send to Primary address only if Secondary address is unavailable
SEND
NONE
Send only to the Primary address
NONE
SEND
Send only to the Secondary address
NONE
NONE
Do not send any alarms to either address