External interlock – Hypertherm Phoenix 8.0 User Manual

Page 564

background image

Edge Ti

557

Pins AMP #1-66506-0
Cabling: Use Belden # 9541

External Interlock

An external interlock is provided to remotely disable servo power.

Interlock Pinout
Pin#
Description
1

Interlock Relay Coil (24VDC)

2 GND
3 GND
4

+24VDC (50 milliamps maximum)


Additional Notes:

1. For Servo Drive Amplifiers to operate, Pin 1 must be connected to GND Pin 2,

typically through a remote mushroom type switch. If no remote switch is to be
used, connect pin 1 to pin 2 with a jumper or the servo drives will not power on.

2. 24VDC is provided for use to activate the digital inputs only in the case where

sourced inputs are selected, it must not be used for any other auxiliary purpose.


Mating Connector
Connector AMP #206060-1
Backshell AMP #206062-3
Sockets 20-24AWG AMP #66105-3

Motor Encoder Connections
Edge Ti supports DC brush and brushless motors. Switch SW1 on the drive interface can
be used to select motor type being used. Please note the location and setting in the
following illustration.

Drive Type selection on Axes Setup screen must be set to CURRENT mode.