Adjusting Voltage and Current Regulation Parameters
9-5
Monitoring the DC Bus Feedback
The DC bus feedback is a measurement of the DC bus voltage. Refer
to Figure 9.4 For a firmware diagram that monitors the DC bus
feedback.
Three different feedback references are available. Each reference
provides the same voltage feedback at a different reference point in
the processor. We recommend that you use the default setting (0) for
P139.
The bus feedback is then scaled. When the feedback select (P219) is
set to "0", the bus feedback is applied to the feedback filter. The
feedback filter is configured using P137 and P138. Finally, P141
provides the DC bus feedback.
Figure 9.4
Firmware Diagram for Monitoring the DC Bus Feedback
kn
256 S + wn
S + wn
Feedback
Scaling
138
137
140
143
16
144
139
1/4
1/4
0
1
2
38
60
61
DC Bus
Feedback
X
X
Y
X
X
X
*
Indirect, parameter X
Source; parameter X
Sink; parameter X
Parameter X, bit Y
Battery-backed, parameter X
SYMBOL KEY
141
Parameter Number
Parameter Name
16
Nominal DC Voltage
38
Host A/D Converter Input 2
60
DSP DC Bus Voltage
61
DSP Averaged DC Bus Voltage
137
Wn, Bus Feedback Filter Bandwidth
138
Kn, Bus Feedback Filter Gain
139
Voltage Input Select
140
Prefiltered Feedback
141
DC Bus Feedback
143
Scaled Bus Feedback
144
Bus Feedback Calibration