Programming Parameters
D-43
204
Internal Capacitance
[Int Capacitance]
This parameter specifies the internal capacitance
of the RGU (determined by the Frame Catalog
Number (P4)). P201 can be used to view the
charge rate of the internal capacitance.
Parameter Type
Source (Read/Write)
Display Units
uF/10
Drive Units
Display Units * 1
Factory Default
See below
Minimum Value
10
Maximum Value
3000
Related Parameters
P201, P203
J-code RGUs
K-code RGUs
L-code RGUs
M-code RGUs
N-Code RGUs
Factory Default
645 (286*)
Factory Default
1200 (600*)
Factory Default
1500
Factory Default
2400
Factory Default
2400
* Value applies to units with 575V AC inputs
205
Voltage Loop Bandwidth
[Bus Voltage BW]
This parameter specifies the bandwidth of the
voltage loop. This value is used by the RGU to
calculate the proportional gain and integral gain in
the PI regulator (P118 and P119).
Parameter Type
Sink (Read/Write)
Display Units
rad/s
Drive Units
Display Units * 1
Factory Default
50.0
Minimum Value
5.00
Maximum Value
500.00
Related Parameters
P206
206
Voltage Loop Damping
[Bus Volt Damping]
This parameter specifies the damping for the
voltage loop. This value is used by RGU to
calculate the proportional gain and integral gain in
the PI regulator (P118 and P119).
Parameter Type
Sink (Read/Write)
Display Units
%
Drive Units
Display Units * 1
Factory Default
100.00
Minimum Value
30.00
Maximum Value
500.00
Related Parameters
P205
207
Bus Voltage Command
[Bus Volt Cmd]
This parameter can be used to specify a
command for the DC bus voltage.
This parameter is used to determine the Bus
Reference (P128) when selected in the Voltage
Mode Select (P123 = 1 or 2, not default).
Parameter Type
Sink (Read/Write)
Display Units
Volt
Drive Units
Display Units * 4096/P16
Factory Default
P16
Minimum Value
0.85 x P16
Maximum Value
1.15 x P16
Related Parameters
P122, P123, P128
208-215
P208-P215 are for internal use only.
215
Simulator Rate
[Simulator Rate]
This parameter defines the rate to be applied to
the bus simulator.
Parameter Type
Sink (Read/Write)
Display Units
%
Drive Units
Display Units * 4096/100
Factory Default
4.88
Minimum Value
0.00
Maximum Value
799.98
Related Parameters
P216, P217, P218
216
Simulator Load
[Simulator Load]
This parameter defines the load to be applied to
the bus simulator.
Parameter Type
Sink (Read/Write)
Display Units
%
Drive Units
Display Units * 5120/100
Factory Default
19.50
Minimum Value
-156.3
Maximum Value
156.3
Related Parameters
P215, P217, P218