Page 188

Publication 2364F-5.01– October 2003
D-44
Programming Parameters
217
Simulator Per Unit Capacitance
[Sim Charge Rate]
This parameter defines the capacitance charge
rate to be applied to the bus simulator.
Parameter Type
Sink (Read/Write)
Display Units
msec
Drive Units
Display Units * 1
Factory Default
32
Minimum Value
20
Maximum Value
2000
Related Parameters
P215, P216, P218
218
Simulated Bus Feedback
[Sim Bus Fdbk]
This parameter indicates the simulated bus
feedback determined by P96 (Iq Reference),
P215, P216, and P217.
This value can be used as the source for P141
(Bus Feedback) when P219 = 1 (not default).
Parameter Type
Source (Read Only)
Display Units
Volt
Drive Units
Display Units * 4096/P16
Factory Default
0.00
Minimum Value
0.00
Maximum Value
1.15 x P16
Related Parameters
P215, P216, P217, P219
219
Feedback Select
[Feedback Select]
This parameter selects the feedback source used
for P141 (Bus Feedback). See P140.
Value Description
0
Bus Volt In
Selects the bus feedback
1
Bus Simulate Selects a simulated feedback
Parameter Type
Source (Read Only)
Display Units
Volt
Drive Units
Display Units * 4096/P16
Factory Default
0
Minimum Value
0
Maximum Value
1
Related Parameters
P215, P216, P217, P219
220-223
P220-P223 are for internal use only.
224
SCANport Port Enable Mask
[Port Enable Mask]
This parameter activates SCANport ports.
SCANport 1 = J10 on main control board
SCANport 2 = J9 on main control board
SCANport 6 = J8 on main control board
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0111 1111
Minimum Value
0000 0000
Maximum Value
0111 1111
Related Parameters
P8, P225, P226, P227
Bit
Description
Bit
Description
0
RGU I/OEnables the RGU I/O port
4
SCANport P:4Enables the port for SCANport 4
1
SCANport P:1Enables the port for SCANport 1
5
SCANport P:5Enables the port for SCANport 5
2
SCANport P:2Enables the port for SCANport 2
6
SCANport P:6Enables the port for SCANport 6
3
SCANport P:3Enables the port for SCANport 3
7
Not Used
225
SCANport Enable Mask
[Enable Mask]
This parameter allows a connected SCANport
device to enable the RGU. The selected ports
must be activated (P224).
Parameter Type
Sink (Read/Write)
Display Units
Bits
Drive Units
Display Units * 1
Factory Default
0111 1111
Minimum Value
0000 0000
Maximum Value
0111 1111
Related Parameters
P8, P224, P226, P227
Bit
Description
Bit
Description
0
RGU I/OEnables the RGU I/O
4
SCANport P:4Enables SCANport 4
1
SCANport P:1Enables SCANport 1
5
SCANport P:5Enables SCANport 5
2
SCANport P:2Enables SCANport 2
6
SCANport P:6Enables SCANport 6
3
SCANport P:3Enables SCANport 3
7
Not Used