226
SCANport Clear Fault Mask
[Clear Fault Mask]
This parameter allows a connected SCANport
device to clear faults in the RGU. The selected
ports must be active (P224).
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0111 1111
Minimum Value
0000 0000
Maximum Value
0111 1111
Related Parameters
P8, P224, P225, P227
Bit
Description
Bit
Description
0
RGU I/OClears RGU I/O faults
4
SCANport P:4Clears SCANport 4 faults
1
SCANport P:1Clears SCANport 1 faults
5
SCANport P:5Clears SCANport 5 faults
2
SCANport P:2Clears SCANport 2 faults
6
SCANport P:6Clears SCANport 6 faults
3
SCANport P:3Clears SCANport 3 faults
7
Not Used
227
SCANport Reset Mask
[Reset Mask]
This parameter allows a connected SCANport
device to reset the RGU. The selected ports must
be active (P224).
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0111 1111
Minimum Value
0000 0000
Maximum Value
0111 1111
Related Parameters
P8, P224, P225, P226
Bit
Description
Bit
Description
0
RGU I/OResets RGU I/O
4
SCANport P:4Resets SCANport 4
1
SCANport P:1Resets SCANport 1
5
SCANport P:5Resets SCANport 5
2
SCANport P:2Resets SCANport 2
6
SCANport P:6Resets SCANport 6
3
SCANport P:3Resets SCANport 3
7
Not Used
228,229
P228 and P229 are for internal use only.
230
SCANport Disable Owner
[Disable Owner]
Parameter Type
Source (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0000 0000 0000 0000
Minimum Value
0000 0000 0000 0000
Maximum Value
0000 0000 0111 1111
Related Parameters
P231, P232
Bit
Description
Bit
Description
0
RGU I/OIndicates that the RGU I/O port is disabled
4
SCANport P:4Indicates that the port for SCANport 4 is disabled
1
SCANport P:1Indicates that the port for SCANport 1 is disabled
5
SCANport P:5Indicates that the port for SCANport 5 is disabled
2
SCANport P:2Indicates that the port for SCANport 2 is disabled
6
SCANport P:6Indicates that the port for SCANport 6 is disabled
3
SCANport P:3Indicates that the port for SCANport 3 is disabled
7-15
Not Used
231
SCANport Enable Owner
[Enable Owner]
Parameter Type
Source (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0000 0000 0000 0000
Minimum Value
0000 0000 0000 0000
Maximum Value
0000 0000 0111 1111
Related Parameters
P230, P232
Bit
Description
Bit
Description
0
RGU I/OIndicates that the RGU I/O port is enabled
4
SCANport P:4Indicates that the port for SCANport 4 is enabled
1
SCANport P:1Indicates that the port for SCANport 1 is enabled
5
SCANport P:5Indicates that the port for SCANport 5 is enabled
2
SCANport P:2Indicates that the port for SCANport 2 is enabled
6
SCANport P:6Indicates that the port for SCANport 6 is enabled
3
SCANport P:3Indicates that the port for SCANport 3 is enabled
7-15
Not Used