Programming Parameters
D-55
298
Trend 1 Operator
[Trend Operator]
This parameter selects the operation to be
performed between trend X (P294 or P295) and
trend Y (P296 or P297). If trending is enabled
(P302), a true result of the operation will cause
the Trend 1 Input parameter value (from P293) to
be passed to the prescribed output (P293).
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0 (GT)
Minimum Value
0
Maximum Value
7
Related Parameters
P293 to P304
299
Trend 1 Sample Rate
[Trend Samp Rate]
This parameter determines the rate of sampling
for the Trend 1 Indirects (P294, P296).
The value of this parameter can be changed in
increments of 0.002 sec.
Parameter Type
Sink (Read/Write)
Display Units
sec
Drive Units
Display Units * 2000
Factory Default
0.000
Minimum Value
0.000
Maximum Value
30.000
Related Parameters
P293 to P304 (See P298)
300
Trend 1 Post Samples
[Trend Post Samp]
This parameter defines the number of samples
(out of 500) to be allocated for post-trigger
sampling.
Pre-samples + Post samples = 500 (0 to 499)
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
10
Minimum Value
0
Maximum Value
499
Related Parameters
P293 to P304 (See P298)
Value Description
Value Description
0
GTSelects the operation [Trend X must be greater than Trend Y].
4
ANDSelects the operation [Trend X AND Trend Y].
1
LTSelects the operation [Trend X must be less than Trend Y].
5
NANDSelects the operation [Trend X NAND Trend Y].
2
EQSelects the operation [Trend X must be equal to Trend Y].
6
ORSelects the operation [Trend X OR Trend Y].
3
NESelects the operation [Trend X must not be equal to Trend Y].
7
NORSelects the operation [Trend X NOR Trend Y].
Trend Sampling
Trend Configure
Trend Status
Pttt
Trend
Parameter
Pxxx
Source
Parameter X
Pyyy
Source
Parameter Y
P295
Trend 1
X Value
P294
Trend 1
Operand
Indirect X
P297
Trend 1
Y Value
P296
Trend 1
Operand
Indirect Y
P298
Trend 1
Operator
X [Operator] Y
P293
Trend 1
Input
Indirect
P304
Trend 1
Output
Indirect
Pmmm
Trend
Output
Parameter
P299
Trend 1
Sample
Rate
P300
Trend 1
Post
Samples
P301
Trend 1
Mode
P302
Trend 1
Select
P303
Trend 1
Status