Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 177
Publication 2364F-5.01– October 2003
Programming Parameters
D-33
161
Meter Reset Hour
[Meter Reset Hour]
This parameter defines the hour when the power
consumption meter should reset
(P32 bit 2 must be set (not default)).
For example, to have the meter automatically
reset on December 31st, 1998 at 11:59pm,
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
23
Related Parameters
P32, P162, P163, P164, P165
P32 bit 2 would need to be set to 1, and the
meter reset parameters would need to be set
as shown in the diagram.
162
Meter Reset Minute
[Meter Reset Minute]
This parameter defines the minute when the
power consumption meter should reset
(P32 bit 2 must be set (not default)).
See P161 for details.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
59
Related Parameters
P32, P161, P163, P164, P165
163
Meter Reset Month
[Meter Reset Month]
This parameter defines the month when the power
consumption meter should reset
(P32 bit 2 must be set (not default)).
See P161 for details.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
1
Minimum Value
1
Maximum Value
12
Related Parameters
P32, P161, P162, P164, P165
164
Meter Reset Day
[Meter Reset Day]
This parameter defines the day when the power
consumption meter should reset (P32 bit 2 must
be set (not default)).
See P161 for details.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
1
Minimum Value
1
Maximum Value
31
Related Parameters
P32, P161, P162, P163, P165
165
Meter Reset Year
[Meter Reset Year]
This parameter defines the year when the power
consumption meter should reset (P32 bit 2 must
be set (not default)).
See P161 for details.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
99
Related Parameters
P32, P161, P162, P163, P164
P164
Meter
Reset Day
P165
Meter
Reset Year
P161
Meter
Reset Hour
P162
Meter
Reset
Minute
P163
Meter
Reset
Month
11:59 pm 12 / 31 / 98
23
59
12
31
98