Programming Parameters
D-63
337
Trend 4 Mode
[Trend Mode]
This parameter determines the duration of the
trending process. The trending process can be
configured to stop trending after a trigger event
occurs (default), or can continue trending.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
1
Related Parameters
P329 to 340 (See also P298)
Value Description
0
One ShotCommands the trending process to stop after a single trigger event.
1
ContinuousCommands the trending process to run continuously.
338
Trend 4 Select
[Trend Select]
This parameter commands the RGU to enable,
disable, or force trigger Trend 4.
After the RGU processes the command, the value
resets to 3 (No Command).
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
3 (No Command)
Minimum Value
0
Maximum Value
3
Related Parameters
P329 to 340 (See also P298)
Value Description
0
DisableCommands the RGU to disable Trend 4.
1
EnableCommands the RGU to enable Trend 4.
2
Force TrigCommands the RGU to force trigger Trend 4. The trending value (prescribed by P329) will be sent to Trend 4 Output Indirect (P340).
3
No CommandIndicates that no command is issued at this time.
339
Trend 4 Status
[Trend Status]
This parameter displays the status of Trend 4.
Parameter Type
Sink (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
1 (Unprogrammed)
Minimum Value
0
Maximum Value
4
Related Parameters
P329 to 340 (See also P298)
Value Description
0
UnprogrammedTrend 4 is not programmed.
1
StoppedThe trending operation is stopped (trend X and trend Y values are not being evaluated).
2
RunningThe trending operation is running (trend X and trend Y values are being evaluated).
3
TriggeredThe trending operation between trend X and trend Y is true. The trending value (determined by P329) will be output through P340.
4
Forced TrigTrend 4 is triggered due to a ‘Force Trig’ command from the Trend 4 Select (P338 = 0). The trending value is output.
340
Trend 4 Output Indirect
[Trend Out Ind]
This parameter prescribes the destination of the
trend parameter value (listed in P329). The
trending operation (X [operator] Y) must be
evaluated as true for P340 to output the value
from the trend source in P329.
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (no selection)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P329 to 339 (See also P298)
341
Number of Trend Samples
[Trend Samples]
This parameter indicates the number of trend
samples taken (up to 500).
Parameter Type
Source (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
500
Minimum Value
0
Maximum Value
500
Related Parameters
P298, P300