Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 148
Publication 2364F-5.01– October 2003
D-4
Programming Parameters
9
RGU State of Operation
[RGU State]
This parameter indicates the RGU’s state of
operation during the power-up sequence and
during normal operation.
Parameter Type
Source (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
9
Related Parameters
None
Value Description
0
HW Init
Indicates that the RGU hardware is initiating (startup or reset)
1
No Bus Voltage
Indicates that the DC bus is not yet powered
2
Precharging
Indicates that the RGU is precharging the capacitors
3
Closing M1
Indicates that precharging is complete and the main contactor M1 is closing
4
Flt, M1 Closed
Indicates that the RGU is faulted, M1 is closed
5
Flt, M1 Open
Indicates that the RGU is faulted, M1 is opened
6
HW Failure
Indicates that hardware failure has occured in the RGU
7
Crtl Ready
Indicates that the RGU control is ready for operation
8
Starting Ctrl
Indicates that the RGU control is starting operation
9
Ctrl Running
Indicates that the RGU control is processing
10
Nominal AC Line Voltage
[Nom Line Voltage]
This parameter stores the nominal input line
voltage of the RGU.
Parameter Type
Source (Read/Write)
Display Units
Vrms
Drive Units
Display Units * 1
Factory Default
See below
Minimum Value
See below
Maximum Value
See below
Related Parameters
P4, P14, P26, P27
RGUs with a 380V AC Input
RGUs with a 460V AC Input
RGUs with a 575V AC Input
Factory Default
380
Factory Default
460
Factory Default
575
Minimum Value
198
Minimum Value
207
Minimum Value
258
Maximum Value
418
Maximum Value
506
Maximum Value
633
Hard Fault
Hardware
Initiate
No Bus
Voltage
Precharging
Closing M1
Fault, M1
Closed
Control
Ready
Fault, M1
Open
Starting
Control
Hardware
Failure
Not Hard
Fault
Hardware
Error
Timeout
Timeout or
Bus Not Up
Not
Hard
Fault
Hard
Fault
Control
Running
Hard Fault
Bus
Up
Not Enabled