Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 200

Publication 2364F-5.01– October 2003
D-56
Programming Parameters
301
Trend 1 Mode
[Trend Mode]
This parameter determines the duration of the
trending process. The trending process can be
configured to stop trending after a trigger event
occurs (default), or can continue trending.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
1
Related Parameters
P293 to P304 (See P298)
Value Description
0
One ShotCommands the trending process to stop after a single trigger event.
1
ContinuousCommands the trending process to run continuously.
302
Trend 1 Select
[Trend Select]
This parameter commands the RGU to enable,
disable, or force trigger Trend 1.
After the RGU processes the command, the value
resets to 3 (No Command).
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
3 (No Command)
Minimum Value
0
Maximum Value
3
Related Parameters
P293 to P304 (See P298)
Value Description
0
DisableCommands the RGU to disable Trend 1.
1
EnableCommands the RGU to enable Trend 1.
2
Force TrigCommands the RGU to force trigger Trend 1. The trending value (prescribed by P293) will be sent to Trend 1 Output Indirect (P304).
3
No CommandIndicates that no command is issued at this time.
303
Trend 1 Status
[Trend Status]
This parameter displays the status of Trend 1.
Parameter Type
Sink (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
1 (Unprogrammed)
Minimum Value
0
Maximum Value
4
Related Parameters
P293 to P304 (See P298)
Value Description
0
UnprogrammedTrend 1 is not programmed.
1
StoppedThe trending operation is stopped (trend X and trend Y values are not being evaluated).
2
RunningThe trending operation is running (trend X and trend Y values are being evaluated).
3
TriggeredThe trending operation between trend X and trend Y is true. The trending value (determined by P293) will be output through P304.
4
Forced TrigTrend 1 is triggered due to a ‘Force Trig’ command from the Trend 1 Select (P302 = 0). The trending value is output.
304
Trend 1 Output Indirect
[Trend Out Ind]
This parameter prescribes the destination of the
trend parameter value (listed in P293). The
trending operation (X [operator] Y) must be
evaluated as true for P304 to output the value
from the trend source.
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (no selection)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P293 to P303 (See P298)
305
Trend 2 Input Indirect
[Trend In Ind]
This parameter designates the parameter to be
output when Trend 2 is triggered (when the trend
X/trend Y evaluation is true).
The source parameter defined here is passed to
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (no selection)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P306 to P316 (See also P298)
the output (P316) when the trending operation is
evaluated as true.