Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 178
Publication 2364F-5.01– October 2003
D-34
Programming Parameters
166-173
P166-P173 are for internal use only.
174
Host Fault Status Word 1
[Fault Status 1]
This parameter indicates a number of host fault
conditions.
1 - Fault
0 - No Fault
Parameter Type
Source (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0000 0000 0000 0000
Minimum Value
0000 0000 0000 0000
Maximum Value
1111 1111 1111 1111
Related Parameters
P175, P176
P175 and P176 determine what conditions are
reported and how the conditions are to be
handled (warning/fault).
Bit
Description
0
ROM Bad CRC Indicates that a ROM fault has been detected.
1
RAM Error
Indicates a fault in the RAM.
2
BatRAM Err
Indicates a fault in the battery-backed RAM.
3
DSP Load
Indicates a DSP loading fault.
4
FPGA Load
Indicates an FPGA loading fault.
5
Iq Foldback
Indicates an Iq foldback fault.
6
M1 Open
Indicates that the M1 contactor has opened (P9).
7
SCANport Err
Indicates an error in the SCANport.
8
R2R HW Error
Indicates an error in the RGU-to-RGU hardware.
9
Control Volt
Indicates a control voltage fault.
10
H/S Overtemp
Indicates that the heatsink temperature (P87) has exceeded maximum.
11
Bus Low
Indicates that the DC bus voltage has fallen below the DC Bus Low Setting (P28).
12
Bus High
Indicates that the DC bus voltage has risen above the DC Bus High Setting (P29).
13
BRAM Chksum Indicates a parity error in the battery-backed RAM.
14
Prchrg Fail
Indicates that the precharge operation has failed.
15
DSP Timeout
Indicates that the DSP has timed out.