Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 168
Publication 2364F-5.01– October 2003
D-24
Programming Parameters
107
DC Bus Current
[DC Bus Current]
This parameter displays the DC bus current,
calculated by the Real Power (P151) and the
Scaled Bus Feedback (P143).
Parameter Type
Source (Read Only)
Display Units
Amps
Drive Units
Display Units * 1
Factory Default
0.0
Minimum Value
0.0
Maximum Value
3276.7
Related Parameters
P143, P151
108
Total Line Current
[Iac Total]
This parameter displays the total AC line current,
calculated from the Iq Feedback (P100), the
Rated AC Line Current (P11), and the Id
Feedback (P106).
Parameter Type
Source (Read Only)
Display Units
Amps
Drive Units
Display Units * 1
Factory Default
0.0
Minimum Value
-3276.7
Maximum Value
3276.7
Related Parameters
P11, P100, P106
109
Notch Filter Freq for Iq Cmd
[Iq Cmd FIR Freq]
Frequency for FIR notch filter applied to value of Iq
current command (P94).
Parameter Type
Source (Read/Write)
Display Units
Hertz
Drive Units
Display Units * 1
Factory Default
0.0
Minimum Value
0.0
Maximum Value
500
Related Parameters
P94
110-114
P110-P114 are for internal use only.
115
Voltage Loop PI Error Limit
[PI Error Limit]
This parameter is used to determine when the
error limiter will activate.
When the value of the Voltage Loop Error (P142)
exceeds the value defined by this parameter,
Parameter Type
Sink (Read/Write)
Display Units
Volt
Drive Units
Display Units * 4096/P16
Factory Default
-34
Minimum Value
-100
Maximum Value
-4
Related Parameters
P35, P116, P117, P142
and when P35 bit 1 = 1 (the Err Limiter bit is
enabled in the Host Mode parameter), then the
error limiter will be activated to provide the
additional error correction needed.
Set this parameter to the desired error value
for activating the error limiter.
116
Voltage Loop Error Limit Step
[PI Err Lim Step]
This parameter determines the step used by the
error limiter.
The P115 listing describes what the error limiter
does, and how it is activated.
Parameter Type
Sink (Read/Write)
Display Units
% of P11
Drive Units
Display Units * 1000/40960
Factory Default
0.0
Minimum Value
-80.0
Maximum Value
0.0
Related Parameters
P115, P117
P117
P116
P115
Err