Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 167

Publication 2364F-5.01– October 2003
Programming Parameters
D-23
103
Id Mode Select
[Id Mode Select]
This parameter selects the Id current reference to
be sent to the Id limiter.
Select the Id limiter input from the list below.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
3
Related Parameters
P93, P101, P102
104
Id Positive Current Limit
[Id Pos Limit]
This parameter determines the maximum value for
the Id Reference (P93). The value of this
parameter is passed to the Id limiter.
This parameter is selected as the source to the
Parameter Type
Sink (Read/Write)
Display Units
% of P11
Drive Units
Display Units * 5120/100
Factory Default
60.0
Minimum Value
0.0
Maximum Value
60.0
Related Parameters
P35, P93, P105
Id limiter when P35 bit 0 = 0 (when the Host Mode,
Regen Only bit is set to zero). This limit
is selected by default.
When P35 bit 0 = 1, this parameter is not used,
and a value of 0% is passed to the Id limiter.
105
Id Negative Current Limit
[Id Neg Limit]
This parameter determines the minimum value for
the Id Reference (P93). The value of this
parameter is passed to the Id limiter.
Parameter Type
Sink (Read/Write)
Display Units
% of P11
Drive Units
Display Units * 5120/100
Factory Default
-40.0
Minimum Value
-40.0
Maximum Value
0
Related Parameters
P93, P104
106
Id Current Feedback
[Id Feedback]
This parameter displays the calculated Id
feedback.
The value of this parameter is used with P100 (Iq
Feedback) and P11 (Rated AC Line Current) to
calculate the Total Line Current (P108).
Parameter Type
Source (Read Only)
Display Units
% of P11
Drive Units
Display Units * 5120/100
Factory Default
0.0
Minimum Value
-60.0
Maximum Value
60.0
Related Parameters
P93, P100, P108
The value is also used (with P100) to trigger
the wire overload (I2t) indicators (P34 and P183).
P103
Id Mode
Select
P101
Auxiliary Id
Command
0
+
+
0
1
2
3
None
Id Command
Aux Id Cmd
Id Cmd + Aux
0
1
2
3
P102
Id Current
Command
Σ
Id Limiter
Value Description
0
None
Selects 0% as the input to the Id limiter.
1
Id Command
Selects the value in P102 (Id Command) as the input
to the Id limiter.
2
Aux Id Cmd
Selects the value in P101 (Auxiliary Id Command) as
the input to the Id limiter.
3
Id Cmd + Aux Selects the sum of P102 (Id Command) and P101
(Auxiliary Id Command) as the input to the Id limiter.