Rockwell Automation 2364F Regenerative DC Bus Supply Unit (RGU) User Manual
Page 203
Publication 2364F-5.01– October 2003
Programming Parameters
D-59
315
Trend 2 Status
[Trend Status]
This parameter displays the status of Trend 2.
Parameter Type
Sink (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
1 (Unprogrammed)
Minimum Value
0
Maximum Value
4
Related Parameters
P305 to P316 (See also P298)
Value Description
0
UnprogrammedTrend 2 is not programmed.
1
StoppedThe trending operation is stopped (trend X and trend Y values are not being evaluated).
2
RunningThe trending operation is running (trend X and trend Y values are being evaluated).
3
TriggeredThe trending operation between trend X and trend Y is true. The trending value (determined by P305) will be output through P316.
4
Forced TrigTrend 2 is triggered due to a ‘Force Trig’ command from the Trend 2 Select (P314 = 0). The trending value is output.
316
Trend 2 Output Indirect
[Trend Out Ind]
This parameter prescribes the destination of the
trend parameter value (listed in P305). The
trending operation (X [operator] Y) must be
evaluated as true for P316 to output the value
from the trend source in P305.
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (no selection)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P305 to P315 (See also P298)
317
Trend 3 Input Indirect
[Trend In Ind]
This parameter designates the parameter to be
output when Trend 3 is triggered.
The source parameter defined here is passed to
the output (P328) when the trending operation is
evaluated as true.
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (no selection)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P318 to P328 (See also P298)
318
Trend 3 Operand Indirect X
[Trend X Ind]
This parameter designates a source parameter to
be analyzed in the Trend 3 evaluation. The
source value is masked with the trend Y value
(P320 or P321).
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (disabled, P319 enabled)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P317 to P328 (See also P298)
P319 (Trend 3 X Value) is used as the trend X
operand when this parameter is zero (default).
319
Trend 3 X Value
[Trend X Value]
This parameter defines a constant to be masked
with the trend Y value (P320 or P321).
To use this parameter, the trend X indirect (P318)
must equal zero.
Parameter Type
Sink (Read/Write)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
-32768
Maximum Value
32767
Related Parameters
P317 to P328 (See also P298)
320
Trend 3 Operand Indirect Y
[Trend Y Ind]
This parameter designates a source parameter to
be analyzed in the Trend 3 evaluation. The
source value masks the trend X value (P318 or
P319). P321 (Trend 3 Y Value) is used as the
trend Y operand when this parameter equals zero.
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (disabled, P321 enabled)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P317 to P328 (See also P298)