342-401
P342-P401 are for internal use only.
402
Signal Processor 1 Input
[SigProc 1 Input]
This parameter indicates the parameter that is to
be processed through Signal Processor 1.
To process a value, set P402 to the parameter to
be processed, set P403 to the destination (where
you want the results), set P405 to the
Parameter Type
Sink (Read/Write)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0 (no selection)
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P403 to P406
offset value that should be applied to the source,
set P404 to the gain that should be applied to
the source value, and set P406 to the cutoff
frequency.
403
Signal Processor 1 Output
[SigProc 1 Output]
This parameter specifies where the results of the
processed value should be placed.
Parameter Type
Source (Read Only)
Display Units
Parameter Number
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
0
Maximum Value
Maximum Defined Parameter Number
Related Parameters
P402 to P406
404
Signal Processor 1 Gain
[SigProc 1 Gain]
This parameter specifies the gain that should be
applied to the source value (indicated in P402).
Note that the offset is applied before the gain.
Parameter Type
Source (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
1.00
Minimum Value
-4.00
Maximum Value
4.00
Related Parameters
P402 to P406
405
Signal Processor 1 Offset
[SigProc 1 Offset]
This parameter specifies the offset to apply to the
source value (indicated in P402).
Note that the offset is applied before the gain.
Parameter Type
Source (Read Only)
Display Units
None
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
-32768
Maximum Value
32767
Related Parameters
P402 to P406
406
Signal Processor 1 Cutoff Frequency
[SigProc 1 Cutoff]
This parameter specifies the cutoff frequency to
be used by the signal processor.
Parameter Type
Source (Read Only)
Display Units
R/S (rad/sec)
Drive Units
Display Units * 1
Factory Default
0
Minimum Value
-32768
Maximum Value
32767
Related Parameters
P402 to P405
P40 2
Signal
Processor 1
Input
P 405
Signal
Processor 1
O ffset
P404
Signal
Processor 1
G ain
P40 6
Signal
Processor 1
Cutoff Freq
P 403
Signal
Processor 1
O utput
+ /- adjustm ent to
source value
m ultiplier to
source value
adjusts the
frequency
specifies
destination
param eter
indicates source
param eter
Psss
S ource
Param eter
Pddd
D estination
P aram eter