Programming Parameters
D-7
27
AC Line High Setting
[Line Hi Setting]
This parameter defines the highest acceptable AC
line voltage. A fault or warning may be indicated
in P180 (Host Fault Status Word 3) if the AC line
voltage exceeds the value of this parameter.
Parameter Type
Sink (Read/Write)
Display Units
Vrms
Drive Units
Display Units * 1
Factory Default
528 (110% of 480V AC)
Minimum Value
0
Maximum Value
800
Related Parameters
P14, P26, P180
RGUs with a 380V AC Input
RGUs with a 460V AC Input
RGUs with a 575V AC Input
Factory Default
436
Factory Default
528
Factory Default
660
28
DC Bus Low Setting
[Bus Low Setting]
This parameter defines the lowest acceptable DC
bus voltage. A fault or warning may be indicated
in P174 (Host Fault Status Word 1) if the DC bus
voltage falls below the value of this parameter.
Parameter Type
Sink (Read/Write)
Display Units
Volt
Drive Units
Display Units * 4096/P16
Factory Default
5/7 * P16
Minimum Value
0
Maximum Value
1.5 * P16
Related Parameters
P16, P29, P141, P174
29
DC Bus High Setting
[Bus Hi Setting]
This parameter defines the highest acceptable DC
bus voltage. A fault or warning may be indicated
in P174 (Host Fault Status Word 1) if the DC bus
voltage exceeds the value of this parameter.
Parameter Type
Sink (Read/Write)
Display Units
Volt
Drive Units
Display Units * 4096/P16
Factory Default
8/7 * P16
Minimum Value
0
Maximum Value
1.5 * P16
Related Parameters
P16, P28, P141, P174
30
DC Bus Voltage Tolerance
[Bus V Tolerance]
This parameter defines the acceptable voltage
tolerance on the DC bus. The DC bus is
considered to be “at voltage” when the value of
P141 (Bus Feedback) is within the range of P126
(Bus Rate Reference) +/- P30.
Parameter Type
Sink (Read/Write)
Display Units
Volt
Drive Units
Display Units * 4096/118
Factory Default
0.005 * P16 (0.5% of P16)
Minimum Value
0
Maximum Value
0.029 * P16 (2.9% of P16)
Related Parameters
P16, P34, P141, P126
When the voltage is within the tolerance, the “Bus
at Volt” bit of P34 (Host Status 2) is set to 1
31
P31 is for internal use only.