Parameter 2125 [interlock code – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 361

Publication 1756-UM522B-EN-P - February 2003
1756-DMF30 Specific Information C-109
Parameter 2125 [Interlock Code]
The PMI processor performs interlock tests in response to parameter
2100 [Drive Ctrl Word]. If any of the diagnostics fail the PMI
processor sets the bit in parameter 2125 [Interlock Code] that
corresponds to the first failed diagnostic. The bit stays latched until
bit 19 [Clear Fault] of parameter 152 [Applied Logic Cmd] or bit 19 [Clr
Drv Wrn] of parameter 166 [Motor Ctrl Cmd] is set. Refer to Reliance
Electric publication S-3001-1, Distributed Power System SD3000 Drive
Diagnostics, Troubleshooting and Start-Up Guidelines, for information
about the interlock diagnostics.
10
SCR 14 Fault
SCR 14 Fault (Reverse Bridge)
11
SCR 15 Fault
SCR 15 Fault (Reverse Bridge)
12
SCR 16 Fault
SCR 16 Fault (Reverse Bridge)
Bit
Fault Name
Fault Description
0
Bad CML Req
More than one incompatible CML operating mode has
been requested at a time in parameter 166 [Motor Ctrl
Cmmd]. The following operating modes are mutually
exclusive:
•••• Armature Alpha Test
•••• Armature Identification Test
•••• CML Run
This bit is also set if you have attempted to restart the
drive without resetting the appropriate command bits
from parameter 166. Note that the bits in register 166
are edge-sensitive.
1
3PhPrmNotLod
Three-phase configuration parameters have not been
downloaded into the PMI module from the Drive
Module
2
3PhGnsNotLod
Three-phase configuration parameters have not been
downloaded into the PMI module from the Dive
Module.
3
3PhFltRstRq
The CML Faults Need to be Reset bit is set if previous
armature faults (parameter 2122 [MC Faults]) have not
been cleared.
4
RPI Missing
The run permissive input on the Resolver & Drive l/O
module is not on.
5
Fld Not Rdy
The single-phase field is not on. Note that the CML
can-not be executed if the field is not on.
6
Fld NotAlwd
The single-phase field has been requested when the
armature identification test or the armature alpha test
is running.
7
M-Con NotCls
The M-Contactor did not close at the expected time.
Bit
Fault Name
Fault Description