Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 345
![background image](/manuals/579192/345/background.png)
Publication 1756-UM522B-EN-P - February 2003
1756-DMF30 Specific Information C-93
2200
PMI Drive Config
Set bits to configure the PMI processor.
• Bits 0-7 [PMI OS Sel] indicate the catalog number of
the Drive Module (do not modify these settings).
• Bit 8 [Arm Reg Used] enables control of the motor
armature.
• Bit 9 [re Bdge Usd] enables control of a regenerative
armature bridge.
• Bit 10 [S12 Config] enables twelve-pulse control.
• Bit 11 [M-Cont Used] enables Drive Module control of
the main contactor.
• Bit 12 [Fld Reg Used] enables control of the motor field.
• Bit 13 [4 quad fld] enables four-quadrant control of the
motor field.
• Bit 14 [3ph fld gene] is not used.
Default:
0000 0000 0000 0001
Options
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bti 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
Arm Reg Used
Rev Bdge Usd
S12 Config
Reserved
Fld Reg Used
4 quad fld
3ph fld gene
Reserved
File:
Group:
DPS/PMI
Drive Config
2201
PMI I/O Config
Set bits to configure the rail I/O and speed feedback in the PMI
processor.
• Bits 0-3 [Prt 0 Config] form a nibble that configures the
port 0 rail I/O
• Bits 4-7 [Prt 1 Config] form a nibble that configures the
port 1 rail I/O: 0 = no I/O, 1 = Digital I/O, 2 = 2 Channel
Analog Input / 2 Channel Analog Output, 3 = 4 Channel
Analog Output, 4 = 4 Channel Analog Input.
• Bits 8-11 [Res Type] form a nibble that configures the
resolver type: 0 = no resolver, 1 = 1 x resolver, 2 = 2 x
resolver, 3 = 5 x resolver.
• Bits 12-15 [SpdFdbk Type] form a nibble that configures
the speed feedback type: 0 = no speed feedback, 1 =
tachometer, 2 = resolver.
Default:
0000 0000 0000 0000
Options
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bti 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Prt 0 Config
Prt 0 Config
Prt 0 Config
Prt 0 Config
Prt 1 Config
Prt 1 Config
Prt 1 Config
Prt 1 Config
Res Type
Res Type
Res Type
Res Type
SpdFdbk Type
SpdFdbk Type
SpdFdbk Type
SpdFdbk Type
File:
Group:
DPS/PMI
Drive Config
2202
AC LineVolt(RMS)
Enter the nominal input voltage to the Armature Power
Module. The PMI processor uses this value to determine the
threshold (15% below this value) for indicating the low AC line
voltage warning.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Volt
230
10
32767
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config
2203
Out Volt Rating
Enter the maximum output voltage the Power Module will
produce.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Volt
10
10
32767
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config
No.
Name
Description
Values