Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 276

Publication 1756-UM522B-EN-P - February 2003
C-24 1756-DMF30 Specific Information
227
PeakDetect2 Out
Output from the second peak/level detector.
Default:
Min:
Max:
Type:
File:
Group:
0
-2200000000
2200000000
Non-Linkable, Read-Only, Floating Point
Utility
Peak Detection
230
Resolver SpdFdbk
Displays speed feedback from the resolver. Select resolver by
entering a value of 0 in of parameter 222 [Motor Fdbk Sel].
Configure the resolver with parameter 2201 [PMI I/O Confg].
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
0
-14000
14000
Non-Linkable, Read-Only, Floating Point
Speed/Posit Fdbk
Resolver
231
Resolver PositFB
Indicates accumulated position feedback generated by the
resolver. This parameter supplies position regulator feedback
if postion control is enabled.
Default:
Min:
Max:
Type:
File:
Group:
0
-32768
32767
Non-Linkable, Read-Only, 16-Bit Integer
Speed/Posit Fdbk
Resolver
240
Anlg Tach Spd FB
Displays speed feedback from an analog tach. Select analog
tach by entering a value of 2 in of parameter 222 [Motor Fdbk
Sel].
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
0
-14000
14000
Non-Linkable
Read-Only, Floating Point Speed/Posit Fdbk
Analog Tach
241
Anlg Tach Posit
Indicates accumulated position feedback generated by the
analog tach. This parameter supplies position regulator
feedback if postion control is enabled.
Default:
Min:
Max:
Type:
File:
Group:
0
-2147483648
2147483648
Non-Linkable, Read-Only, 32-Bit Integer
Speed/Posit Fdbk
Analog Tach
300
Motor Spd Fdbk
Displays measured motor speed information from the selected
feedback device. A value of 1.0 represents base speed of the
motor.
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
0
-14000
14000
Non-Linkable, Read-Only, Floating Point
Monitor, Speed/Posit Fdbk
Metering, Feedback Config
305
3Ph FieldCurrRef
Displays the value of current reference that is present at the
output of the current rate limiter. 100% is equal to 1 per unit
(pu) rated drve current.
Units:
Default:
Min:
Max:
Type:
File:
Group:
P.U.
0
-8
8
Non-Linkable, Read-Only, Floating Point
Field Control
Current
No.
Name
Description
Values