Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 155
![background image](/manuals/579192/155/background.png)
Publication 1756-UM522B-EN-P - February 2003
1756-DMD30 Specific Information B-75
371
Mtr OL Trip Cnfg
Enter a value to configure the drive's response to a “Motor
Overload Trip” exception event.
• Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
• Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
• Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
• Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
• Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default
Val 2
FltCoastStop
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
372
Mtr OL Pend Cnfg
Enter a value to configure the drive's response to a “Motor
Overload Pending” exception event.
• Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
• Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
• Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
• Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
• Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default
Val 1
Alarm
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
373
Motor Stall Time
Enter or write a value to specify the time delay between when
the drive detects a “Motor Stall” condition and when it
declares the exception evet.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Sec
5
0.1
3000
Linkable, Read-Write, Floating Point
Utility
Fault/Alm Config
374
Motor Stall Cnfg
Enter a value to configure the drive's response to a “Motor
Stall” exception event.
• Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
• Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
• Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
Default
Val 0
Ignore
Options:
Val 0
Val 1
Val 2
Ignore
Alarm
FltCoastStop
File:
Group:
Utility
Fault/Alm Config
No.
Name
Description
Values