Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 157

Publication 1756-UM522B-EN-P - February 2003
1756-DMD30 Specific Information B-77
383
Lgx Timeout Cnfg
Enter a value to configure the Drive Module's response to a
Controller to Drive Module connection timeout, as detected by
the Drive Module.
• Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
• Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
• Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
• Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
• Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default
Val 2
FltCoastStop
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
No.
Name
Description
Values
ATTENTION
!
Risk of injury or equipment damage exists. Parameter 383 [Lgx Timeout Cnfg]
lets you determine the action of the drive if communications are disrupted.
By default this parameter causes the drive to fault and coast to a stop. You
can set this parameter so that the drive continues to run. Precautions should
be taken to ensure that the setting of this parameter does not create a hazard
of injury or equipment damage.