Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 327
![background image](/manuals/579192/327/background.png)
Publication 1756-UM522B-EN-P - February 2003
1756-DMF30 Specific Information C-75
1233
SL BOF Error
Displays the number of BOF errors that occurred during the last
test (last 8 mS). This data is visable on the SynchLink
diagnostics tab of the Peer Communication window.
Default:
Min:
Max:
Type:
File:
Group:
0
0
4294967296
Non-Linkable, Read-Only, 32-Bit Integer
Utility
Diagnostics
1234
SL CRC Err Limit
The number of CRC errors per test (per 8 mS) allowed before
the drive declares a SynchLink CRC Error exception event. Set
this limit on the SynchLink diagnostics tab of the Peer
Communication window.
Default:
Min:
Max:
Type:
File:
Group:
2
0
256
Non-Linkable, Read-Write, 32-Bit Integer
Utility
Diagnostics
1235
SL BOF Err Limit
The number of BOF errors per test (per 8 mS) allowed before
the drive declares a SynchLink BOF Error exception event. Set
this limit on the SynchLink diagnostics tab of the Peer
Communication window.
Default:
Min:
Max:
Type:
File:
Group:
2
0
256
Non-Linkable, Read-Write, 32-Bit Integer
Utility
Diagnostics
2000
DM Com Prt Stat
Indicates faults or warnings related to the Drive Module’s
Drive Communication ports.
• Bit 0 [Bad Rcv Int] indicates the interrupt generated by
the Universal Serial Controller (USC) is not properly
marked
• Bit 1 [No EOF] indicates the USC did not report an End
of Frame condition when the recieve interrupt was
generated
• Bit 2 [CRC Error] indicates the USC has reported a
Cyclic Redundancy Check (CRC) error on the last frame
(message) received
• Bit 3 [Overrun Err] indicates the USC has reported a
receive firs-in, first out error
• Bit 4 [DMA Error] indicates the length of a received
message did not match the length encoded in the
message itself
• Bit 5 [Xmit Underun] indicates the USC has reported a
transmit first-in, first-out underrun
• Bit 6 [Sync Error] indicates two or more CCLK counter
ticks occurred and no message was recieved
• Bit 7 [LoopBack Err] indicates failure in the loopback
test (the transmit message did not match the receive
message). The Drive Module performs this test on
power-up and reset.
• Bit 8 [Missed Gains] indicates gain data could not be
written because memory was being written to when
the gain values were received
• Bit 9 [Multplx Err] indicates data which is multiplexed
into a command/feedback message has not verified
correctly
Default:
0000 0000 0000 0000
Options:
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bad Rcv Int
No EOF
CRC Error
Overrun Err
DMA Error
Xmit Underun
Sync Error
LoopBack Err
Missed Gains
Multplx Err
No PMI OS
Bad OS Hdr
Bad PMI HW
Reserved
Reserved
Reserved
File:
Group:
DPS/PMI
DPS/PMI
• Bit 10 [No PMI OS] indicates the correct PMI operating
system is not present in the Drive Module and the PMI
is requesting an operating system
• Bit 11 [Bad OS Hdr] indicates the Drive Module cannot
locate a valid PMI operating system header when
attempting to load an operating system to a PMI
• Bit 12 [Bad PMI HW] indicates PMI hardware is not
compatible with the PMI operating systems in the
Drive Module
No.
Name
Description
Values