B-80 1756-DMD30 Specific Information
387
SL MultErr Cnfg
Enter a value to configure the Drive Module's response to
SynchLink Multiplier error. Refer to parameter 1034 [SL Mult
State] for possible causes for multiplier errors.
• Value 0 - Ignore configures the drive module to
continue running as normal, in response to this event
• Value 1 - Alarm configures the drive module to set the
appropriate alarm bit in response to this event
• Value 2 - FltCoastStop configures the drive module to
perform a coast stop and set the appropriate fault bit in
response to this event
• Value 3 - FltRampStop configures the drive module to
perform a ramp stop and set the appropriate fault bit in
response to this event
• Value 4 - CurLimStp configures the drive module to
perform a current limit stop and set the appropriate
fault bit in response to this event
Default
Val 2
FltCoastStop
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp
File:
Group:
Utility
Fault/Alm Config
396
User Data 1
General purpose parameter available for storage of 32 bit
integer data by the operator. This value will be retained
through a power cycle.
Default:
Min:
Max:
Type:
File:
Group:
0
-2147483648
2147483648
Non-Linkable, Read-Write, 32-bit Integer
Utility
User Selections
397
User Data 2
General purpose parameter available for storage of 32 bit
integer data by the operator. This value will be retained
through a power cycle.
Default:
Min:
Max:
Type:
File:
Group:
0
-2147483648
2147483648
Non-Linkable, Read-Write, 32-bit Integer
Utility
User Selections
No.
Name
Description
Values
ATTENTION
!
Risk of injury or equipment damage exists. Parameter 387 [SL MultErr Cnfg]
lets you determine the action of the drive if communications are disrupted.
By default this parameter causes the drive to fault and coast to a stop. You
can set this parameter so that the drive continues to run. Precautions should
be taken to ensure that the setting of this parameter does not create a hazard
of injury or equipment damage.