Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 344
![background image](/manuals/579192/344/background.png)
Publication 1756-UM522B-EN-P - February 2003
C-92 1756-DMF30 Specific Information
2182
3Ph Hot Fld Curr
Set to the 3Ph field current rating full load amps.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
1
1
3276.7
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Motor Data
2184
PMI Curr Lim
Provides positive and negative current limit values within the
PMI processor. If this value is les than parameter 120[Current
PosLimit] and the absolute value of parameter 119 [Current
NegLimit], this value will set both the positive and negative
actual current limits.
Units:
Default:
Min:
Max:
Type:
File:
Group:
%
100
100
400
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Motor Data
2185
Hot Field Curr
Set to the Hot Amps value on the motor nameplate.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0.01
0.01
327.67
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Motor Data
2186
Min Field Curr
Set to the minimum amps value on the motor nameplate.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0.01
0.01
99.99
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Motor Data
2187
Field Loss Amps
Set the under-current trip point for field loss detection in the
PMI processor.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0.01
0.01
99.99
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Motor Data
2188
Field Off Delay
Set the amount of time the field will remain energized after a
fault condition. (1 to 300S)
Units:
Default:
Min:
Max:
Type:
File:
Group:
Sec
1
1
300
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Motor Data
No.
Name
Description
Values