Parameter 2124 [pwr device status – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 360

Publication 1756-UM522B-EN-P - February 2003
C-108 1756-DMF30 Specific Information
Parameter 2124 [Pwr Device Status]
The bits of this parameter indicate which SCR has shorted or not
firing. If an SCR is shorted parameter 2122 [MC Faults] bit 0 [SCR
Fault] will be set. If an SCR is not firing correctly parameter 2123 [MC
Warnings] bit 0 [BrdgNotFirng]will be set.
For a regenerative drive, this parameter indicates the pair of SCRs that
has faulted. For a non-regenerative drive, this parameter indicates the
specific SCR that has faulted.
The bits of this parameters are set when a fault event is detected.
They stay latched until bit 19 [Clear Fault] of parameter 152 [Applied
Logic Cmd] or bit 19 [Clr Drv Wrn] of parameter 166 [Motor Ctrl Cmd]
is set. If the fault event remains present, the identifying bit is set
again.
12
PMI Fan Loss
Airflow through the PMI rack is not being sensed. A
solid-state airflow switch in the PMI power supply
monitors airflow.
13
Rail IO Comm
A rail communication warning event has occurred.
Parameter 2044 [Rail Port 0 Faul] and parameter 2050
[Rail Port 0 Faul] enumerate these faults.
14
PMI CommSync The PMI Processor and the Drive Module are
momentarily not synchronized.
15
PMI Comm
A fiber-optic communication error has been detected
between the PMI Processor module and the Drive
Module. Communication errors in two consecutive
messages will cause a fault.
Bit
Fault Name
Fault Description
0
SCR 1 Fault
SCR 1 Fault (Forward Bridge)
1
SCR 2 Fault
SCR 2 Fault (Forward Bridge)
3
SCR 3 Fault
SCR 3 Fault (Forward Bridge)
4
SCR 4 Fault
SCR 4 Fault (Forward Bridge)
5
SCR 5 Fault
SCR 5 Fault (Forward Bridge)
6
SCR 6 Fault
SCR 6 Fault (Forward Bridge)
7
SCR 11 Fault
SCR 11 Fault (Reverse Bridge)
8
SCR 12 Fault
SCR 12 Fault (Reverse Bridge)
9
SCR 13 Fault
SCR 13 Fault (Reverse Bridge)
Bit
Fault Name
Fault Description