Parameter data in linear list format – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 266
Publication 1756-UM522B-EN-P - February 2003
C-14 1756-DMF30 Specific Information
Parameter Data In Linear List Format
No.
Name
Description
Values
111
Curr Ref 1
Supplies an external current reference to the drive. This
parameter is divided by the value inparameter 112 [Curr Ref1
Div]. A value of 1.0 represents rated current of the drive.
Default:
Min:
Max:
Type:
File:
Group:
0
-2200000000
2200000000
Linkable, Read-Write, Floating Point
Field Control
Current
112
Curr Ref1 Div
The divisor for parameter 111 [Curr Ref 1].
Default:
Min:
Max:
Type:
File:
Group:
1
-2200000000
2200000000
Non-Linkable, Read-Write, Floating Point
Field Control
Current
113
Curr Ref 2
Supplies an external current reference to the drive. This
parameter is multiplied by the value in [Curr Ref2 Mult]. A
value of 1.0 represents rated current of the drive.
Default:
Min:
Max:
Type:
File:
Group:
0
-2200000000
2200000000
Linkable, Read-Write, Floating Point
Field Control
Current
114
Curr Ref2 Mult
The multiplier for parameter 113 [Curr Ref 2].
Default:
Min:
Max:
Type:
File:
Group:
1
-2200000000
2200000000
Linkable, Read-Write, Floating Point
Field Control
Current
115
Current Trim
The amount added to the Current Reference before the Speed -
Torque Mode Selector. A value of 1.0 represents rated current
of the drive.
Units:
Default:
Min:
Max:
Type:
File:
Group:
P.U.
0
-8
8
Linkable, Read-Write, Floating Point
Field Control
Current
150
Logic State Mach
Indicates the logical state of the drive.
Value 0 - Stopped indicates zero speed has been detected and
the speed and torque regulators are disabled.
Default:
0
Zero
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Val 5
Val 6
Stopped
Starting
Running
Stopping
Inertia Test
MC Diag
Reserved
File:
Group:
Monitor
Control Status