Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 248
Publication 1756-UM522B-EN-P - February 2003
B-168 1756-DMD30 Specific Information
5
ID TestAbort
The drive has failed an armature identification test, field
identification test or resolver balance calibration test.
6
Fld OvrCurr
Field current has exceeded 150% of the value in parameter
2185 [Hot Field Curr].
7
Arm Fdbk Rev
Armature feedback wiring is reversed - the polarity of the
feedback is the oposite of expected.
8
CT Fdbk Rev
Current transformer feedback is reversed - the polarity of
the feedback is the oposite of expected.
12
PMI Fan Loss
Airflow through the PMI rack is not being sensed. A
solid-state airflow switch in the PMI power supply monitors
airflow.
13
Rail IO Comm
A rail communication warning event has occurred.
Parameter 2044 [Rail Port 0 Faul] and parameter 2050 [Rail
Port 0 Faul] enumerate these faults.
14
PMI CommSync
The PMI Processor and the Drive Module are momentarily
not synchronized.
15
PMI Comm
A fiber-optic communication error has been detected
between the PMI Processor module and the Drive Module.
Communication errors in two consecutive messages will
cause a fault.
Bit
Fault Name
Fault Description