Parameter 2050 [rail port 1 faults – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 357
Publication 1756-UM522B-EN-P - February 2003
1756-DMF30 Specific Information C-105
Parameter 2050 [Rail Port 1 Faults]
This parameter indicates the occurance of faults associtated with Rail
I/O on Port 1.
Bit
Fault Name
Fault Description
0
Ch0 OvrRange
Analog input on channel 0 is over the maximum
value.
(1)
(1)
Analog 4 input 4-20 mA (model number 61C345) maximum value = 22.1 mA
Analog 4 input 0-10V (model number 61C346) maximum value = 11.3V
Analog 2 input / 2 ouput 4-20 mA (model number 61C345) maximum value = 22.6 mA
Analog 2 input / 2 ouput 0-10V (model number 61C346) maximum value = 11.3V
1
Ch0 UndRange
Analog input on channel 0 is under the minimum
value.
(2)
(2)
Analog 4 input 4-20 mA (model number 61C345) minimum value = 2.4 mA
Analog 4 input 0-10V (model number 61C346) minimum value = -1.0V
Analog 2 input / 2 ouput 4-20 mA (model number 61C345) minimum value = 2.5 mA
Analog 2 input / 2 ouput 0-10V (model number 61C346) minimum value = -1.0V
2
Ch1 OvrRange
Analog input on channel 1 is over the maximum
value.
3
Ch1 UndRange
Analog input on channel 1 is under the minimum
value.
4
Ch2 OvrRange
Analog input on channel 2 is over the maximum
value.
5
Ch2 UndRange
Analog input on channel 2 is under the minimum
value.
6
Ch3 OvrRange
Analog input on channel 3 is over the maximum
value.
7
Ch3 UndRange
Analog input on channel 3 is under the minimum
value.
8
Port NotCntd
No device is connected to the port, which is
configured to accept a device.
9
Bad ID
A device other than a rail is plugged into the port.
10
Bad Chk Bits
Bad rail communication check bits have been
received.
11
IO NotRdy
The I/O interface is not ready.