Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 140
![background image](/manuals/579192/140/background.png)
Publication 1756-UM522B-EN-P - February 2003
B-60 1756-DMD30 Specific Information
220
Spd Observer BW
Sets the internal bandwidth for the speed feedback observer.
The setting should be as high a possible, preferrably at least 6
times the value of parameter 90 [Spd Reg BW]. A setting of
1000 rad/sec is reasonable for most applications. The speed
observer is bypassed when set to zero.
Units:
Default:
Min:
Max:
Type:
File:
Group:
R/S
0
0
300
Linkable, Read-Write, Floating Point
Speed/Posit Fdbk
Feedback Config
221
Load Estimate
Displays the estimated load torque, which is the side effect of
the speed observer and does not include torque to accelerate
or decelerate the motor if the inertia input is correct. The value
is provided for display purposes.
Units:
Default:
Min:
Max:
Type:
File:
Group:
P.U.
0
-8
8
Non-Linkable, Read Only, Floating Point
Speed/Posit Fdbk
Feedback Config
222
Motor Fdbk Sel
Enter or write a value to select the primary motor speed
feedback device.
Default:
Val 0
Resolver
Options:
Val 0
Val 1
Val 2
Val 3
Val 4
Val 5
Resolver
Analog Tach
Reserved
Reserved
Motor Sim
Mtr Voltage
File:
Group:
Speed/Posit Fdbk
Feedback Config
227
PeakDetect2 Out
Output from the second peak/level detector.
Default:
Min:
Max:
Type:
File:
Group:
0
-2200000000
2200000000
Non-Linkable
Read Only
Floating Point
Utility
Peak Detection
230
Resolver SpdFdbk
Displays speed feedback from the resolver. Select resolver by
entering a value of 0 in of parameter 222 [Motor Fdbk Sel].
Configure the resolver with parameter 2201 [PMI I/O Confg].
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
0
-14000
14000
Non-Linkable, Read Only, Floating Point
Speed/Posit Fdbk
Resolver
231
Resolver PositFB
Indicates accumulated position feedback generated by the
resolver. This parameter supplies position regulator feedback
if postion control is enabled.
Default:
Min:
Max:
Type:
File:
Group:
0
-32768
32767
Non-Linkable, Read Only, 16-bit Integer
Speed/Posit Fdbk
Resolver
240
Anlg Tach Spd FB
Displays speed feedback from an analog tach. Select analog
tach by entering a value of 2 in of parameter 222 [Motor Fdbk
Sel].
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
0
-14000
14000
Non-Linkable, Read Only, Floating Point
Speed/Posit Fdbk
Analog Tach
No.
Name
Description
Values