Parameter 1229 [sl error status – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual
Page 355
![background image](/manuals/579192/355/background.png)
Publication 1756-UM522B-EN-P - February 2003
1756-DMF30 Specific Information C-103
Parameter 1229 [SL Error Status]
This parameter indicates the occurance of SynchLink errors.
Bit
Fault Name
Fault Description
0
Sync Loss
SynchLink communication has failed, after it had
been established.
1
Rx Loss
The receive port is not receiving data, and the receive
port configuration is set to receive data.
2
Many BOF Err
The number of BOF (Beginning Of Frame) errors
accumulated in parameter 1232 [SL BOF Err Accum]
exceeds the value in parameter 1235 [SL BOF Err
Limit].
3
Many CRC Err
The number of CRC (Cycling Ring Checksum) errors
accumulated in parameter 1230 [SL CRC Err Accum]
exceeds the value in parameter 1234 [SL CRC Err
Limit].
4
Pckg Msg Err
The received package sequence number has not
matched for 1.0 S.
5
CommForm Err
The format of received data does not match the
configuration of the receive port.
6
Sys Rev Err
The system revision in received data does not match
the value of parameter 1001 [SynchLink Rev].
7
Mult TKeeper
More than one node on the SynchLink system is
configured as a Time Keeper.