B-148 1756-DMD30 Specific Information
2163
CML Ref Rate
Controls the current reference ramp block within the PMI
processor. Leave at default for most applications, which sets
the rate equal to parameter 354[Curr Rate Limit].
Default:
Min:
Max:
Type:
File:
Group:
4095
1
4095
Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2180
Motor NP RPM
Set to the motor nameplate rated RPM.
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
1750
1
30000
Non-Linkable, Read-Write, 16-bit Integer
Torque Control
Current
2181
Overspd Trip Pt
Set the overspeed trip point for overspeed detection in the PMI
processor.
Units:
Default:
Min:
Max:
Type:
File:
Group:
RPM
2000
1
30000
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2182
Motor NP FLA
Set to the motor nameplate full load amps.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
1
1
3276.7
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2183
Motor NP Volts
Set to the motor nameplate rated volts.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Volt
1
1
32767
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2184
PMI Curr Lim
Provides positive and negative current limit values within the
PMI processor. If this value is les than parameter 120[Current
PosLimit] and the absolute value of parameter 119 [Current
NegLimit], this value will set both the positive and negative
actual current limits.
Units:
Default:
Min:
Max:
Type:
File:
Group:
%
100
100
400
Non-Linkable, Read-Write, 16-bit Integer
DPS/PMI
Motor Data
2185
Hot Field Curr
Set to the Hot Amps value on the motor nameplate.
Units:
Default:
Min:
Max:
Type:
File:
Group:
Amps
0.10
0.01
327.67
Non-Linkable, Read-Write, 16-bit Integer
Speed Control
Regulator
No.
Name
Description
Values