1336 FORCE AC Drive User Manual
Pages 3–20 through 3–24
GPT information does not apply.
Page 5–31
Important note added to “Drive Link Baud Rate” description.
Important: If a v6.xx drive is added to the
drive link that has v5.xx or less, it will only
operate at 125k baud. If all drives on the
drive link are v6.xx, it can operate at 250k
and 500k baud.
Drive Link Baud Rate
[D2D Baud Rate]
Parameter Number
10
Parameter Type
Sink
Display Units
Kbaud
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
2
This word parameter specifies the baud
rate used on the drive-to-drive link (CAN)
communication interface as follows:
00H = 125K baud
01H = 250K baud
02H = 500K baud
www.rockwellautomation.com