Rockwell Automation 1336T FORCE Series B User Manual
Page 210
Chapter 5
Programming Parameters
5–84
Pulse Value
[Pulse Value]
Parameter Number
399
Parameter Type
Source
Display Units
x.x RPM
Drive Units
4096 = Pulse Scale
Factory Default
0.0
Minimum Value
–8 x Pulse Scale
Maximum Value
+8 x Pulse Scale
This parameter displays the pulse input
value.
Pulse Offset
[Pulse Offset]
Parameter Number
398
Parameter Type
Sink
Display Units
x.x RPM
Drive Units
None
Factory Default
0.0
Minimum Value
– Pulse Scale
Maximum Value
+ Pulse Scale
This parameter determines the minimum
speed the pulse input will go to.
This parameter determines the pulse input
speed that is equal to 4096 drive units.
Pulse Scale
[Pulse Scale]
Parameter Number
397
Parameter Type
Sink
Display Units
x RPM
Drive Units
4096
Factory Default
1750
Minimum Value
–6000
Maximum Value
+6000
SP Comm Retries
[SP Comm Retries]
Parameter Number
404
Parameter Type
Source
Display Units
x.
Drive Units
Factory Default
0.0
Minimum Value
0
Maximum Value
65535
This parameter monitors the amount of
SCANport communications errors
that have occurred since power up.
Pulse PPR
[Pulse PPR]
Parameter Number
395
Parameter Type
Sink
Display Units
x PPR
Drive Units
None
Factory Default
1024
Minimum Value
500
Maximum Value
20000
This parameter determines the pulse input
pulses per revolution.
Pulse Single or Double Edge
[Pulse Edge]
Parameter Number
396
Parameter Type
Sink
Display Units
None
Drive Units
None
Factory Default
1
Minimum Value
1
Maximum Value
2
Enums:
1 = 1 Edge
2 = 2 Edges
This parameter determines if rising (single)
or rising and falling (double) edges are