Rockwell Automation 1336T FORCE Series B User Manual
Page 167
Chapter 5
Programming Parameters
5–41
Logic Testpoint Select
[Logic Tstpt Sel]
Parameter Number
71
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
30
Enums:
This parameter selects which internal loca-
tion in the logic control software will be-
come the testpoint value shown in P70.
The value based upon the select will be
stored in the Logic Tstpnt Data parameter.
The internal locations of the logic control
software accessible based on the select
value are:
Select Value
Logic Access Point
0
Zero
1
Logic State
2
Edge Filtered Logic Command
3
Logic Control Word
4
Flux Inhibit Conditions
5
Run Inhibit Conditions
6
Current Processor Command Word
7
Current Processor Status Word
8
Diagnostic Request Flag
9
Requested Torque Mode
10
Contactor Fault Flag
11
Monitor Sample
12
Sys Status
13
Loss of CP Enable Acknowledge
14
Last Stop
15
Stop Event
Select Value
Logic Access Point
16
Diagnostic Inhibit bits
17
Common Bus Precharge States
18
Contactor Trip Condition
19
Adapter handshake counter
20
Longest handshake count
21
Stop event – LED state
22
Stop event – System mode register
23
Stop event – Fault stop command
24
Stop event – Powerup diagnostic status
25
Stop event – Nonconfigurable fault status
26
Stop event – Current Processor Config Fault Status
27
Stop event – Velocity Processor Config Fault Status
28
Stop event – Adapter fault status
29
Stop event – Logic Command (parameter 52)
30
Stop event – Local Inputs (parameter 54)
Stop Dwell
[Stop Dwell]
Parameter Number
72
Parameter Type
Sink
Display Units
x.x sec
Drive Units
Display units x 10
Factory Default
0.0 sec
Minimum Value
0.0 sec
Maximum Value
10.0 sec
This sets an adjustable dwell time before
the drive disables speed and torque regu-
lators when a stop has occurred.
Maximum Dynamic Brake Power
[Max DB Power]
Parameter Number
77
Parameter Type
Sink
Display Units
x Watts
Drive Units
None
Factory Default
0 Watts
Minimum Value
0 Watts
Maximum Value
30,000 Watts
Maximum Dynamic Brake Temperature
[Max DB Temp]
Parameter Number
78
Parameter Type
Sink
Display Units
x deg
Drive Units
None
Factory Default
50 deg
Minimum Value
50 deg
Maximum Value
700 deg
Dynamic Brake Time Constant
[DB Time Const]
Parameter Number
79
Parameter Type
Sink
Display Units
x Sec
Drive Units
None
Factory Default
10 sec
Minimum Value
10 sec
Maximum Value
600 sec
This parameter defines the power rating
for the optional Dynamic Brake resistor.
This value is used to calculate the per unit
R theta for the resistor.
This parameter defines the Maximum Tem-
perature Rating for the optional Dynamic
Brake resistor. This value is used to estab-
lish setpoints for setting and clearing a
Brake Overtemperature fault condition.
This parameter defines the thermal time
constant for the Optional Dynamic Brake
resistor. This value is used in the brake
resistor thermal model to predict brake
temperature as a function of regenerative
power.
NOTE: Caution should be used
when changing the dwell time
from the factory setting.
Extended dwell times may not be
desirable from a safety standpoint
in some applications.