Rockwell Automation 1336T FORCE Series B User Manual
Page 204

Chapter 5
Programming Parameters
5–78
Milli Amp Input Offset
[mA Input Offset]
Parameter Number
362
Parameter Type
Sink
Display Units
+ x.xxx mA
Drive Units
128 = 1mA
Factory Default
+0.000 mA
Minimum Value
–32.000 mA
Maximum Value
+32.000 mA
This parameter determines the offset ap-
plied to the raw analog value of the milli
amp input before the scale factor is ap-
plied. This allows the user to shift the
range of the analog input.
Milli Amp Input Scale
[mA Input Scale]
Parameter Number
363
Parameter Type
Sink
Display Units
+/– x.xxx
Drive Units
2048 = 1
Factory Default
+2.000
Minimum Value
–16.000
Maximum Value
+16.000
This parameter determines the scale factor
or gain for the milli amp input. The milli
amp input is converted to a +/– 2048 and
then the scale is applied which allows an
effective digital range of +/– 32767.
SCANport Analog1 Select
[SB Analog Sel]
Parameter Number
364
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
1
Minimum Value
1
Maximum Value
6
Enums:
This parameter selects which SCANport
analog device is used in parameter 365
‘SP Analog In’.
1
SCANport 1
2
SCANport 2
3
SCANport 3
4
SCANport 4
5
SCANport 5
6
SCANport 6
SCANport Analog1 In
[SB Analog1 In]
Parameter Number
365
Parameter Type
Source
Display Units
+/– x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
This parameter displays the analog value
of the SCANport device selected in
parameter 364 ‘SP Analog Sel’.
SP Analog1 Scale
[SB Analog1 Scale]
Parameter Number
366
Parameter Type
Sink
Display Units
+/–x
Drive Units
+/– 1, 1 = 32767
Factory Default
1 (32767)
Minimum Value
–1 (–32767)
Maximum Value
1 (32767)
This parameter can be used to scale the
value in Parameter 365.