Chapter 5
Programming Parameters
5–35
Process Trim KP Gain
[Proc Trim Kp ]
Process Trim Low Limit
[Proc Trim Lo Lmt]
Process Trim High Limit
[Proc Trim Hi Lmt]
Parameter Number
35
Parameter Type
Sink
Display Units
+/– x.x%
Drive Units
4096 = 100% trim
Factory Default
– 100%
Minimum Value
– 800%
Maximum Value
+ 800%
Parameter Number
34
Parameter Type
Sink
Display Units
+/– x.x%
Drive Units
4096 = 100% trim
Factory Default
–100.0%
Minimum Value
–800.0%
Maximum Value
+800.0%
Process Trim Output Gain
[Proc Trim Out K]
Parameter Number
36
Parameter Type
Sink
Display Units
+/– x.xx
Drive Units
2048 = +1.00 gain
Factory Default
+ 1.00
Minimum Value
– 16.00
Maximum Value
+ 16.00
Parameter Number
37
Parameter Type
Source
Display Units
+/– x
Drive Units
None
Factory Default
+0
Minimum Value
–32767
Maximum Value
+32767
Parameter Number
33
Parameter Type
Sink
Display Units
x.xxx
Drive Units
4096 = 1.0000 Kp gain
Factory Default
1.000
Minimum Value
0.000
Maximum Value
16.000
Process Trim Testpoint
[Proc Trim TP]
This parameter controls the proportional
gain of the process trim regulator. If the
KP process trim is equal to 1.0, then the
process trim PI regulator output will equal 1
pu for 1 pu process trim error.
The output of the process trim regulator is
limited by adjustable high and low limits.
This parameter specifies the low limit of the
process trim output value.
The output of the process trim regulator is
limited by adjustable high and low limits.
This parameter specifies the high limit of
the process trim output value.
This parameter selects which location of
the Process Trim Controller will become
the testpoint value as follows:
Value
Process Trim Access Point
0
Zero
1
Process Trim Error
2
Process Trim Filter Output
3
Process Trim Control Word
The output of the process trim regulator is
scaled by a gain factor. This occurs just
before the upper and lower limit. This pa-
rameter specifies the gain value to use.
Process Trim Testpoint Select
[Proc Trim TP Sel]
This parameter indicates the value of the
internal location selected by the Process
Trim Testpoint Select parameter.
Parameter Number
38
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
3
Enums:
Auto Tune Torque Limit
[Auto Tune Torque]
Parameter Number
40
Parameter Type
Sink
Display Units
x.x %
Drive Units
4096 @ rated motor torque
Factory Default
50.0 %
Minimum Value
25.0 %
Maximum Value
100.0 %
This parameter specifies the motor torque
that is applied to the motor during the
Velocity motor test and the Velocity system
test. 4096 = 100% rated motor torque.