Rockwell Automation 1336T FORCE Series B User Manual
Page 198
![background image](/manuals/578410/198/background.png)
Chapter 5
Programming Parameters
5–72
Data Out C1
[Data Out C1]
Data Out B2
[Data Out B2]
This parameter displays the drive to
SCANport image which is sent to some
device on SCANport
Parameter Number
323
Parameter Type
Sink
Display Units
+/–x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
Parameter Number
324
Parameter Type
Sink
Display Units
+/–x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
This parameter displays the drive to
SCANport image which is sent to some
device on SCANport
Data Out D1
[Data Out D1]
This parameter displays the drive to
SCANport image which is sent to some
device on SCANport
Parameter Number
326
Parameter Type
Sink
Display Units
+/–x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
Data Out C2
[Data Out C2]
Parameter Number
325
Parameter Type
Sink
Display Units
+/–x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
This parameter displays the drive to
SCANport image which is sent to some
device on SCANport
Data Out D2
[Data Out D2]
This parameter displays the drive to
SCANport image which is sent to some
device on SCANport
Parameter Number
327
Parameter Type
Sink
Display Units
–/–x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
SCANport Port Enable Mask
[Port Enable Mask]
Parameter Number
330
Parameter Type
Sink
Display Units
Bits
Drive Units
None
Factory Default
0111 1111
Minimum Value
0000 0000
Maximum Value
0111 1111
Enums:
This parameter selects which SCANport
devices can control the Drive.
1 = Permit Control
0 = Deny Control
Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2
Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5
Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved