Chapter 2
Installation/Wiring

2–18

Shielded type wire is recommended in control circuits for protection
against interference. A shielded wire is required for all signal wires. The
recommended conductor size must be a minimum of 16 AWG. The best
interference suppression is obtained with a wire having an individual shield
for every twisted pair. Figure 2.9 shows recommended cable shielding.

Figure 2.9.
Cable Shielding Recommendations

1241

1242

3682

3683

8271

8281

8291

8301

8311

8321

2 Conductor
Shielded Cable

2 Conductor Shielded Cable

Multi-Conductor Shielded
Cable with Individual
Shielded twisted Pairs

Shield

Shield

Shield

TE

TE

TE

Shield Connection

Lug Kits

D,E,F, and G frame drives have stud type terminals and/or bus bars/bolts
that require standard crimp–type connectors for cable termination.
Connectors such as T&B COLOR–KEYED

Connectors or equivalent are

recommended. Table 2.C shows the lug selection for one possible cable
choice. Choose connectors for each installation based on the desired cable
sizes, the application requirements, and all applicable national, state, and
local codes.