Rockwell Automation 1336T FORCE Series B User Manual
Page 203

Chapter 5
Programming Parameters
5–77
10 Volt Input
[10 Volt Input]
Parameter Number
355
Parameter Type
Source
Display Units
+/– x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
This parameter displays the converted
analog value of the +/– 10 volt input.
10 Volt Offset
[10 Volt Offset]
Parameter Number
356
Parameter Type
Sink
Display Units
+/– x.xx volt
Drive Units
205 = 1 volt
Factory Default
+0.00 volt
Minimum Value
–20.00 volt
Maximum Value
+20.00 volt
This parameter determines the offset ap-
plied to the raw analog value of the +/– 10
volt input before the scale factor is applied.
This allows the user to shift the range of
the analog input.
10 Volt Scale
[10 Volt Scale]
Parameter Number
357
Parameter Type
Sink
Display Units
+/– x.xxx
Drive Units
2048 = 1
Factory Default
+2.000
Minimum Value
–16.000
Maximum Value
+16.000
This parameter determines the scale factor
or gain for the +/– 10 volt input. The +/– 10
volt input is converted to +/– 2048 and
then the scale is applied which allows an
effective digital range of +/– 32767.
Pot Input
[Pot Input]
Parameter Number
358
Parameter Type
Source
Display Units
+/– x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
This parameter displays the converted
analog value of the pot input.
Pot Offset
[Pot Offset]
Parameter Number
359
Parameter Type
Sink
Display Units
+/– x.xx volts
Drive Units
205 = 1 volt
Factory Default
+0.000 volt
Minimum Value
–20.000 volt
Maximum Value
+20.000 volt
This parameter determines the offset
applied to the raw analog value of the pot
input before the scale factor is applied.
This allows the user to shift the range of
the of the analog input.
Pot Scale
[Pot Scale]
Parameter Number
360
Parameter Type
Sink
Display Units
+/– x.xxx
Drive Units
2048 = 1
Factory Default
+1.000
Minimum Value
–16.000
Maximum Value
+16.000
This parameter determines the scale factor
or gain for the pot input. The pot input is
converted to a +/– 2048 and then the scale
is applied allowing an effective digital range
of +/– 32767
Milli Amp Input
[mA Input]
Parameter Number
361
Parameter Type
Source
Display Units
x
Drive Units
None
Factory Default
+0
Minimum Value
0
Maximum Value
+32767
This parameter displays the converted
analog value of the milli amp input.