Rockwell Automation 1336T FORCE Series B User Manual
Page 209

Chapter 5
Programming Parameters
5–83
MOP Value
[Mop Value]
Parameter Number
394
Parameter Type
Source
Display Units
x RPM
Drive Units
4096 = Base Speed
Factory Default
0.0
Minimum Value
Negative Speed Limit
Maximum Value
Positive Speed Limit
This parameter displays the MOP value.
I/O Deceleration Rate 2
[Decel Rate 2]
Parameter Number
392
Parameter Type
Sink
Display Units
x.x sec
Drive Units
10 = 1 sec
Factory Default
10.0 sec
Minimum Value
0.0 sec
Maximum Value
6553.5 sec
This parameter determines the base speed
to 0 rpm ramp rate.
Mop Increment
[Mop Increment]
Parameter Number
393
Parameter Type
Sink
Display Units
x.x RPM (RPM per sec)
Drive Units
4096= Base Speed
Factory Default
10% of base speed
Minimum Value
0.0 RPM
Maximum Value
Base Speed
This parameter determines the rate of
increase or decrease to the MOP value
per time.
I/O Deceleration Rate 1
[Decel Rate 1]
Parameter Number
391
Parameter Type
Sink
Display Units
x.x sec.
Drive Units
10 = 1 sec
Factory Default
10.0 sec
Minimum Value
0.0 sec
Maximum Value
6553.5 sec
This parameter determines the base speed
to 0 rpm ramp rate.
I/O Acceleration Rate 2
[Accel Rate 2]
Parameter Number
390
Parameter Type
Sink
Display Units
x.x sec
Drive Units
10 = 1 sec
Factory Default
10.0 sec
Minimum Value
0.0 sec
Maximum Value
6553.5 sec
This parameter determines the 0 rpm to
base speed ramp rate.
I/O Stop Select 2
[Stop Select 2]
Parameter Number
388
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
3
This parameter selects the stopping mode
for a valid stop command.
3 = Param 59 Bits 4 or 5
2 = Current limit stop
1 = Ramp Stop
0 = Coast Stop
I/O Acceleration Rate 1
[Accel Rate 1]
This parameter determines the 0 rpm to
base speed ramp rate.
Parameter Number
389
Parameter Type
Sink
Display Units
x.x Sec
Drive Units
10 = 1 sec
Factory Default
10 sec
Minimum Value
0.0 sec
Maximum Value
6553.5 sec