Rockwell Automation 1336T FORCE Series B User Manual
Page 194
Chapter 5
Programming Parameters
5–68
Kp Frequency Regulator
[Kp Freq Reg]
Parameter Number
288
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
800
Minimum Value
0
Maximum Value
32767
Proportional gain of the frequency regula-
tor in sensorless mode. This parameter
must not be changed.
Kff Freq Regulator
[Kff Freq Reg]
Parameter Number
289
Parameter Type
Sink
Display Units
x
Drive Units
1 = 256
Factory Default
1
Minimum Value
0
Maximum Value
128
Ksel Freq Regulator
[Ksel Freq Reg]
Feedforward gain of the frequency regula-
tor in sensorless mode. This parameter
must not be changed.
Parameter Number
290
Parameter Type
Sink
Display Units
x.x
Drive Units
None
Factory Default
67
Minimum Value
0.0
Maximum Value
32767
Low frequency gain boost of the frequency
regulator in sensorless mode. This param-
eter must not be changed.
Frequency Tracker Filter
[Freq Track Filt]
Parameter Number
291
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
5000
Minimum Value
0
Maximum Value
32767
Rotor frequency regulator filter in sensor-
less mode. This parameter must not be
changed.
Tracking Filter Type
[Track Filt Type]
Parameter Number
292
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
1 (Self Adjust)
Minimum Value
0 (Fixed)
Maximum Value
128
Frequency Trim Filter
[Freq Trim Filt]
Low frequency filter select of the frequency
regulator in sensorless mode. This param-
eter must not be changed by non–factory
personnel.
Parameter Number
293
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
5000
Minimum Value
0
Maximum Value
32767
Slip frequency regulator filter in sensorless
mode. This parameter must not be
changed.
Motor Phase Rotation Errors
[Phs Test Rot Err]
Parameter Number
294
Parameter Type
Source
Display Units
Bit
Drive Units
None
Factory Default
0000 0000 0000 0000
Minimum Value
0000 0000 0000 0000
Maximum Value
1111 1111 1111 1111
Enums:
This parameter indicates an error condition
detected during the motor phase rotation
test.
1 = Drive condition true
0 = Drive condition false
Bits are defined as:
Bit
Condition
0
1 to 15
Enable Drop Out
Reserved