Rockwell Automation 1336T FORCE Series B User Manual
Page 32

Chapter 2
Installation/Wiring
2–12
Table 2.A
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)
Drive Catalog
Number
kW (HP) Rating
200–240V
Rating
380–480V
Rating
500–600V
Rating
UL Class CC, T, J
1
– BS88 (non-UL installations)
1336T– _ _ F10
0.75 (1)
10A
6A
–
1336T– _ _ F30
2.2 (3)
25A
15A
–
1336T– _ _ F50
3.7 (5)
40A
20A
–
1336T– _ _ 001
0.75 (1)
10A
6A
6A
1336T– _ _ 003
2.2 (3)
15A
10A
10A
1336T– _ _ 007
5.5 (7.5)
40A
20A
15A
1336T– _ _ 010
7.5 (10)
50A
30A
20A
1336T– _ _ 015
11 (15)
70A
35A
25A
1336T– _ _ 020
15 (20)
100A
45A
35A
1336T– _ _ 025
18.5 (25)
100A
60A
40A
1336T– _ _ 030
22 (30)
125A
70A
50A
1336T– _ _ 040
30 (40)
150A
80A
60A
1336T– _ _ 050
37 (50)
200A
100A
80A
1336T– _ _ X060
45 (60)
–
100A
–
1336T– _ _ 060
45 (60)
250A
125A
90A
1336T– _ _ 075
56 (75)
–
150A
110A
1336T– _ _ 100
75 (100)
–
200A
150A
1336T– _ _ 125
93 (125)
–
250A
175A
1336T– _ _ X150
112 (150)
–
250A
–
1336T– _ _ 150
112 (150)
–
300A
225A
1336T– _ _ 200
149 (200)
–
400A
350A
1336T– _ _ 250
187 (250)
–
450A
400A
1336T– _ _ X300
224 (300)
–
–
400A
Bussmann FWP/Gould Shawmut A–70C Semi–conductor Type
1336T– _ _ X250
187 (250)
–
450A
–
1336E– _ _ P250
2
187 (250)
–
450A
2
–
1336T– _ _ 300T
224 (300)
–
450A
400A
1336E– _ _ 300
2
224 (300)
–
500A
2
450A
1336T– _ _ 350
261 (350)
–
500A
450A
1336E– _ _ 350
2
261 (350)
–
600A
2
1336T– _ _ 400
298 (400)
–
600A
500A
1336E– _ _ 400
2
298 (400)
–
600A
2
1336T– _ _ 450
336 (450)
–
800A
600A
1336E– _ _ 450
2
336 (450)
–
700A
2
600A
1336T– _ _ 500
373 (500)
–
800A
800A
1336T– _ _ 600
448 (600)
–
900A
800A
1336T– _ _ 650
485 (650)
–
–
800A
1336T– _ _ 700C
2
522 (700)
–
600A
3
700A
3
1336T– _ _ 800C
2
597 (800)
–
700A
3
700A
3
1 Both fast acting and slow blow are acceptable
2 Fuses are supplied with F and H Frame drives