Appendix B
Adapter Parameters
18
[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if any of the
following is true:
• Device parameter 15 [Comm Flt Action] is set to ‘4’ (Send
Flt Cfg) and I/O communication is disrupted.
• Device parameter 16 [Idle Flt Action] is set to ‘4’ (Send Flt
Cfg) and the controller is idle.
Default:
0
Minimum:
-3.40282 x 10
38
Maximum:
3.40282 x 10
38
Type:
Read/Write
Reset Required:
No
19
20
21
22
[Flt Cfg DL 1]
[Flt Cfg DL 2]
[Flt Cfg DL 3]
[Flt Cfg DL 4]
Sets the data that is sent to the Datalink in the drive if any of the
following is true:
• Device parameter 15 [Comm Flt Actn] is set to 4 “Send Flt
Cfg” and the I/O Communication is disrupted.
• Device parameter 16 [Idle Flt Actn] is set to 4 “Send Flt Cfg”
and the controller is set into Program or Idle mode.
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
23
[DSI I/O Act]
Indicates which drives the 25-COMM-D is communicating with,
in both single-drive and multi-drive modes.
Values:
0 = Drive 0 Actv
1 = Drive 1 Actv
2 = Drive 2 Actv
3 = Drive 3 Actv
4 = Drive 4 Actv
Type:
Read Only
Reset Required:
No
Parameter
No.
Name and Description
Details