Rockwell Automation Publication 520COM-UM002A-EN-E - April 2013

89

Troubleshooting

Chapter 8

The event queue can contain up to 32 entries, which are stored in RAM—
making the event queue volatile, meaning a power cycle will clear the event queue.
If the event queue becomes full, a new entry replaces the oldest entry. Only a
power cycle, event queue clear operation, or the corruption of the RAM group
containing the event queue will clear the event queue contents.

Many events in the event queue occur under normal operation. If you encounter
unexpected communications problems, the events may help you or Allen-Bradley
personnel troubleshoot the problem. The following events may appear in the
event queue:

Adapter Events

Code

Event

Description

Adapter Events

1

No Event

Text displayed in an empty event queue entry.

2

Device Power Up

The adapter was powered up normally.

3

Device Reset

The adapter was commanded to reset from the network or DSI.

4

EEPROM CRC Error

The EEPROM checksum/CRC is incorrect. The functionality of the adapter will be
limited. Default parameter values must be loaded to clear this condition.

5

App Updated

The adapter application firmware was flash updated.

6

Boot Updated

The adapter boot firmware was flash updated.

7

Watchdog Timeout

The software watchdog detected a failure and reset the adapter.

DSI Events

10

DSI Detected

The adapter detected that the DSI device is connected.

11

DSI Removed

The adapter detected that the DSI device was disconnected.

12

DSI Logon

The adapter has established communications with the DSI device.

13

DSI Timeout

The adapter has lost communications with the DSI device.

14

DSI Brand Flt

The brand of the DSI device is different from the adapter.

15

Host 0 Logon

The adapter has established communications with host 0.

16

Host 1 Logon

The adapter has established communications with host 1.

17

Host 2 Logon

The adapter has established communications with host 2.

18

Host 3 Logon

The adapter has established communications with host 3.

19

Host 4 Logon

The adapter has established communications with host 4.

20

Host 0 Timeout

The adapter has lost communications with host 0.

21

Host 1 Timeout

The adapter has lost communications with host 1.

22

Host 2 Timeout

The adapter has lost communications with host 2.

23

Host 3 Timeout

The adapter has lost communications with host 3.

24

Host 4 Timeout

The adapter has lost communications with host 4.

25

Host 0 Brand Flt

The brand of host 0 is different from the adapter.

26

Host 1 Brand Flt

The brand of host 1 is different from the adapter.

27

Host 2 Brand Flt

The brand of host 2 is different from the adapter.

28

Host 3 Brand Flt

The brand of host 3 is different from the adapter.

29

Host 4 Brand Flt

The brand of host 4 is different from the adapter.

30

Manual Reset

The adapter was reset manually.

Network Events

40

Net Link Up

24V power was regained on DeviceNet. DeviceNet communication can be re-
established.

41

Net Link Down

24V power was lost on DeviceNet. DeviceNet communication is impossible.

42

Net Dup Address

The adapter uses the same IP address as another device on the network.

43

Net Comm Fault

The adapter detected a communications fault on the network and has performed the
“Comm Flt” action specified by the user.

44

Net Sent Reset

The adapter received a reset from the network.