Compactlogix example using generic profile – Rockwell Automation 25-COMM-D PowerFlex 525 DeviceNet Adapter User Manual
Page 74
74
Rockwell Automation Publication 520COM-UM002A-EN-E - April 2013
Chapter 7
Using Multi-Drive Mode
•
Control the drives using various Logic Command bits (Stop, Start, etc.)
and Reference.
•
Perform a single parameter read and write for each drive. The example uses
PowerFlex 4M drive parameter P109 [Accel Time 1] for both so you can
see (read) the change after a write is performed.
Drive 0 (PowerFlex 525) Settings for the Example Program
•
Parameter C169 [MultiDrv Sel] is set to 1 “Network Opt”.
•
The following parameters are set:
Drive 1...4 (PowerFlex 4M) Settings for the Example Program (in all
drives)
The following parameters are set:
CompactLogix Example Using
Generic Profile
The following common Tags are used:
Parameter
Value
Description
P046 [Start Source 1]
4
“Network Opt”
P047 [Speed Reference1]
4
“Network Opt”
C175 [DSI I/O Cfg]
4
“Drive 0-4” (5 drives on 1 node)
C171 [Drv 1 Addr]
(1)
(1) The settings for these parameters must match the node address settings in the respective daisy-chained drives.
1
Modbus address of Drive 1
C172 [Drv 2 Addr]
2
Modbus address of Drive 2
C173 [Drv 3 Addr]
3
Modbus address of Drive 3
C174 [Drv 4 Addr]
4
Modbus address of Drive 4
Value
Parameter
Drive 1
Drive 2
Drive 3
Drive 4
P106 [Start Source]
5
5
5
5
P108 [Speed Reference]
5
5
5
5
C302 [Comm Data Rate]
4
4
4
4
C303 [Comm Node Addr]
1
2
3
4
C304 [Comm Loss Action]
0
0
0
0
C305 [Comm Loss Time]
5.0 s
5.0 s
5.0 s
5.0 s
C306 [Comm Format]
0
0
0
0
IMPORTANT
Cycle drive power after making these settings.
Tag Name
Type
Description
Local:1:O
AB:1769_SDN_364Bytes:O:0
1769-SDN I/O
Local:1:I
AB:1769_SDN_496Bytes:I:0
Accel_Time_1
INT
–
Drive_Input_Image
INT [10]
Input Image Table
Drive_Output_Image
INT [10]
Output Image Table