Chapter 7

Using Multi-Drive Mode

Control the drives using various Logic Command bits (Stop, Start, etc.)
and Reference.

Perform a single parameter read and write for each drive. The example uses
PowerFlex 4M drive parameter P109 [Accel Time 1] for both so you can
see (read) the change after a write is performed.

Drive 0 (PowerFlex 525) Settings for the Example Program

Parameter C169 [MultiDrv Sel] is set to 1 “Network Opt”.

The following parameters are set:

Drive 1...4 (PowerFlex 4M) Settings for the Example Program (in all
drives)

The following parameters are set:

CompactLogix Example Using
Generic Profile

The following common Tags are used:

Parameter

Value

Description

P046 [Start Source 1]

4

“Network Opt”

P047 [Speed Reference1]

4

“Network Opt”

C175 [DSI I/O Cfg]

4

“Drive 0-4” (5 drives on 1 node)

C171 [Drv 1 Addr]

(1)

(1) The settings for these parameters must match the node address settings in the respective daisy-chained drives.

1

Modbus address of Drive 1

C172 [Drv 2 Addr]

2

Modbus address of Drive 2

C173 [Drv 3 Addr]

3

Modbus address of Drive 3

C174 [Drv 4 Addr]

4

Modbus address of Drive 4

Value

Parameter

Drive 1

Drive 2

Drive 3

Drive 4

P106 [Start Source]

5

5

5

5

P108 [Speed Reference]

5

5

5

5

C302 [Comm Data Rate]

4

4

4

4

C303 [Comm Node Addr]

1

2

3

4

C304 [Comm Loss Action]

0

0

0

0

C305 [Comm Loss Time]

5.0 s

5.0 s

5.0 s

5.0 s

C306 [Comm Format]

0

0

0

0

IMPORTANT

Cycle drive power after making these settings.

Tag Name

Type

Description

Local:1:O

AB:1769_SDN_364Bytes:O:0

1769-SDN I/O

Local:1:I

AB:1769_SDN_496Bytes:I:0

Accel_Time_1

INT

Drive_Input_Image

INT [10]

Input Image Table

Drive_Output_Image

INT [10]

Output Image Table