Resetting the adapter, Restoring adapter parameters to factory defaults – Rockwell Automation 25-COMM-D PowerFlex 525 DeviceNet Adapter User Manual

Page 30

background image

30

Rockwell Automation Publication 520COM-UM002A-EN-E - April 2013

Chapter 3

Configuring the Adapter

Resetting the Adapter

Changes to switch settings on some adapter parameters require that you reset the
adapter before the new settings take effect. You can reset the adapter by cycling
power to the drive or by using

Device parameter 14 [Reset Module].

Set

Device parameter 14 [Reset Module] to 1 “Reset Module”.

When you enter 1 “Reset Module”, the adapter will be immediately reset. An
alternate method to reset the adapter is by power cycling the drive.

Restoring Adapter
Parameters to Factory
Defaults

Set

Device parameter 14 [Reset Module] to 2 “Set Defaults”.

When you enter 2 “Set Defaults”, the adapter will set all of its parameters to their
factory default values.

ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting control I/O to the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting the adapter.

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

IMPORTANT

When performing a Set Defaults action, the drive may detect a conflict and
then not allow this function to occur. If this happens, first resolve the conflict
and then repeat a Set Defaults action. Common reasons for a conflict include
the drive running or a controller in Run mode.

After performing a Set Defaults action, you must enter 1 “Reset Module” or
power cycle the drive so that the new values take effect. Thereafter, this
parameter will be restored to a value of 0 “Ready”.